3029TF1292.9L Generator Drive Engine
- PowerTech™ M
- Standby: 42-48 kW (56-64 hp) @ 1500-1800 rpm
- Prime: 38-44 kW (51-59 hp) @ 1500-1800 rpm
- Dual frequency available
Features
Features
Expand All
Collapse All
- Induction-hardened journals for long hours of reliable service
- Robust design to drive machinery from the front of the crankshaft
- Supported by five main bearings
- 45-degree connecting rod/cap-joint design allows the use of large connecting rod bearings for increased durability
- Provide excellent heat dissipation
- Precision machined for long life
- Rebuild to original specifications
- Front and rear engine mounting pads on the side of the block facilitates installations
- All connection points in common locations make it easy to install or package
- Short length is ideal for both skid and packaged installations
- High mount or low mount turbocharger position to meet packaging requirements
- Excellent fuel economy and low oil consumption
- Proven and Reliable Mechanical Governor
- 3-5% Droop Governing
- 12V or 24V Electric Shutoff
Specifications
Specifications
General engine data
Model |
3029TF129 |
|
|
|
Number of cylinders |
3 |
|
|
|
Displacement-- L (cu in) |
2.9 (177) |
|
|
|
Bore and Stroke-- mm (in) |
106 x 110 (4.17 x 4.33) |
|
|
|
Compression Ratio |
17.2:1 |
|
|
|
Engine Type |
In-line, 4-Cycle |
|
|
|
Aspiration |
Turbocharged |
|
|
|
Length - mm (in) |
716 (28.2) |
|
|
|
Width-- mm (in) |
519 (20.4) |
|
|
|
Height-- mm (in) |
819 (32.2) |
|
|
|
Weight, dry - kg (lb) |
316 (697) |
|
|
|
Performance data range
Hz (rpm) |
50 ( 1500 ) |
|
|
|
Generator Efficiency % |
88-92 |
|
|
|
Power Factor |
0.8 |
|
|
|
Engine power - Prime kW |
38 |
|
|
|
Engine power - Prime hp |
51 |
|
|
|
Engine power - Standby kW |
42 |
|
|
|
Engine power - Standby hp |
56 |
|
|
|
Rated Fan Power - kW |
2 |
|
|
|
Rated Fan Power - hp |
2.7 |
|
|
|
Calculated generator set output - Prime kWe |
32-33 |
|
|
|
Calculated generator set output - Prime kVA |
40-41 |
|
|
|
Calculated generator set output - Standby kWe |
35-37 |
|
|
|
Calculated generator set output - Standby kVA |
44-46 |
|
|
|
Resources
Resources
Confidence is Built In
Backed by a powerful support network