- UTILITY VEHICLES
- Gator™ Utility Vehicles
- Gator™ UV Attachments
- TOOLS
- Home & Workshop Products
EPA Tier 3 |
---|
EU Stage III A |
Specifications |
||||
---|---|---|---|---|
Select up to 4 models to compare specifications | John Deere 4045HFG82 4.5L Generator Drive Engine |
EPA Tier 3 | ||||
---|---|---|---|---|
EU Stage III A |
Model | 4045HFG82 | |||
---|---|---|---|---|
Number of cylinders | 4 | |||
Displacement-- L (cu in) | 4.5 (275) | |||
Bore and Stroke-- mm (in) | 106 x 127 (4.17 x 5.00) | |||
Compression Ratio | 19.0 : 1 | |||
Engine Type | In-line, 4-cycle | |||
Aspiration | Turbocharged and air-to-air aftercooled | |||
Length - mm (in) | 860 (33.9) | |||
Width-- mm (in) | 612 (24.1) | |||
Height-- mm (in) | 1039 (40.9) | |||
Weight, dry - kg (lb) | 491 (1082) |
Hz (rpm) | 60 ( 1800 ) 50 ( 1500 ) |
|||
---|---|---|---|---|
Generator Efficiency % | 88-92 88-92 |
|||
Power Factor | 0.8 0.8 |
|||
Engine power - Prime kW | 77-115 76-112 |
|||
Engine power - Prime hp | 103-154 102-150 |
|||
Engine power - Standby kW | 85-126 83-123 |
|||
Engine power - Standby hp | 114-169 111-165 |
|||
Rated Fan Power - kW | 10.3-15.5 7.0-9 |
|||
Rated Fan Power - hp | 13.8-20.8 9.4-12.1 |
|||
Calculated generator set output - Prime kWe | 54-96 59-97 |
|||
Calculated generator set output - Prime kVA | 68-120 73-121 |
|||
Calculated generator set output - Standby kWe | 61-107 65-107 |
|||
Calculated generator set output - Standby kVA | 76-133 81-134 |